1 Category: direct shutdown | 1a: automated shutdown | TUjk = t100→0%PNshutdown+ tcondition+ tpreparation+ MTTR+ tre-identification+ treach100%PN | Xjk = λjk × TUjk |
1b: hand-operated shutdown | TUjk = t100→0%PNhand-operated+ tcondition+ tpreparation+ MTTR + tre-identification+ treach100%PN |
1c: hand-operated shutdown after power reduction | TUjk = α·tdiagnosis+ t100→0%PNnormal+ tcondition+ tpreparation+ MTTR + t re-identification + treach100%PN |
2 Second category: power reduction | 2a: maintenance during power reduction | TUjk = α·(MTTR + tre-identification) |
2b: power reduction to next shutdown | TUjk =α·t diagnosis +t100→0%PNnormal+ tcondition + tpreparation+MTTR + t re-identification +treach100%PN |
3 Third category: OTS requirements | 3a: failures that cannot be repaired in RP mode of operational equipment | TUjk = t100→0%PNnormal+ tcondition+ tpreparation+ MTTR + tre-identification+ treach100%PN |
3b: stand-by component failure | TUjk = 1 ≤ t100→0%PNnormal + tcondition + MTTRi + tre-identification + treach100%PN |